These pipes are designed for heavy duty (hd) applications. These conduits are intended to be used in electrical distribution systems inside buildings.
TUBELEC® IRL 4431 1250 N /5cm
TUBELEC ® Electrical conduits are manufactured in compliance with requirements of the European and Lebanese Standard NL- EN 61 386 (parts 1 & 21). Heavy Metal Free (RoHS). The text of the International Standard IEC 61386:2008was approved by CENELEC as a European Standard without any modification.
Main characteristics
Designation of standard conduits:
Conduits are designed according to their mechanical characteristics with a code:
3 or 4 letters +4 digits: ABCD XXXX
Resistance to compression | Resistance to impact | Lower temp. range | Upper temp. range | ||||||
N/5cm | J | °C | °C | ||||||
1 | Very light | 125 | 1 | Very light | 0.5 | 1 | +5 | 1 | 60 |
2 | Light | 320 | 2 | Light | 1 | 2 | -5 | 2 | 90 |
3 | Medium | 750 | 3 | Medium | 2 | 3 | -15 | 3 | 105 |
4 | Heavy | 1250 | 4 | Heavy | 6 | 4 | -25 | 4 | 120 |
5 | Very heavy | 4000 | 5 | Very heavy | 20 | 5 | -45 | 5 | 150 |
Coding example for a TUBELEC® heavy duty (hd) IRL4431 conduit.
Very light : Not accepted for Rigid UPVC conduits
Light conduit systems are not allowed in Europe
Heavy Duty hd *IRL 4431 Standard conduit Colour: Grey-White | Normal size | Out diameter mm | Wall thickness mm | Min. int. diameter mm | Pack qty | Total L |
16 hd | +0 16-0.3 | 1.5 | 12.6 | 50 | 145.0 | |
20 hd | +0 20 -0.3 | 1.7 | 16.4 | 32 | 92.8 | |
25 hd | +0 25 -0.4 | 1.8 | 21.2 | 19 | 55.1 | |
32 hd | +0 32 -0.4 | 2.1 | 26.7 | 14 | 40.6 | |
40 hd | +0 40 -0.4 | 2.2 | 35.6 | 8 | 23.2 |
*IRL = Isolant Rigide Lisse (F) Insuulated Rigid Smooth Conduit